Lucent Technologies Lineage
®
2000 ECS/GPS Battery Plant J85500G-2
Issue 6 May 1999 Product Description 2 - 21
Table 2-I: List 34 Fuse Panel
The List 34 fuse panel houses 3 individual fuse blocks,, each
accommodating a single fuse. Two of the blocks take a (70-100A) load fuse
which is ordered on a job basis. The third block is furnished with a fuse and
shunt (110-200A) by specifying one of the letter lists below.
Load Fuse
Type
Capacity (Amps) Order Information
NON
70-100
110
125
150
175
200
J85500G-2, L-34
L-AY
L-AZ
L-BB
L-BB
L-BC
Table 2-J: List 35 Fuse Panel
The List 35 fuse panel contains 2 individual fuse blocks, each
accommodating a single fuse (70-600A) arranged for load monitoring
shunts and head assemblies ordered by number and list from this table.
Load fuses are ordered on a job basis,separately from the battery plant
order.
Type Capacity (Amps) Ordering Information
Fuse Blocks
NON
70-250
300-600
L-BP
L-BQ
Load Monitoring Shunts
NON
150
300
600
L-BS
L-BU
L-BX
Load Fuses
Type Capacity (Amps) Ordering Information
TPL-BA
TPL-BD
TPL-BF
TPL-BH
TPL-BK
TPL-BL
TPL-CN
TPL-CR
TPL-CV
TPL-CZ
70
100
150
200
225
250
300
400
500
600
406794776
406794784
406794792
406794818
406794982
406794842
406794867
406794875
406794883
406794891

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lucent Technologies Lineage 2000 and is the answer not in the manual?

Lucent Technologies Lineage 2000 Specifications

General IconGeneral
BrandLucent Technologies
ModelLineage 2000
CategoryPower Supply
LanguageEnglish

Related product manuals