EasyManua.ls Logo

Lucent Technologies Lineage 2000 - Table 3-E: Single Hole Terminal Lugs

Lucent Technologies Lineage 2000
127 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Lucent Technologies Lineage
®
2000 ECS/GPS Battery Plant J85500G-2
Issue 6 May 1999 Engineering, Planning and Ordering 3 - 19
Order pre-engineered battery cable kits for use with VR batteries
in supplemental bays can be ordered with the ECS battery plant.
These kits have been engineered for the typical ECS
configurations presented in the J85500G-2 drawing. The kits
contain the following items:
Appropriate length and gauge of KS20921 wire
Appropriate lugs for termination at the battery and at the dc
distribution
Crimping information
Heat shrink tubing
For nontypical ECS configurations where the supplementary
bays are not located adjacent to the initial bay, battery cables
must be engineered to fit the individual installation.
A wide range of circuit breakers and fuses is available for dc
distribution overcurrent protection. The ratings of these circuit
breakers are from 5-600 amperes and the ratings of thge fuses are
from 1-200 amperes. The breaker or fuse rating for a given circuit
is selected by the criteria covered above under Overcurrent
Protection.
Table 3-E: Sin
g
le Hole Terminal Lu
g
s
KS-5482
Wire
KS-20921
Wire
WP-91412
List
Comcode Bolt Size Die
10 10 93 406338145 10 R5473-5
8 8 1 405347402 10 Red
8 8 74 405356189 0.250 Red
6 6 2 405347436 0.250 Blue
4 4 4 405347543 0.250 Grey
2 - 53 405348186 0.250 Brown
- 2 7 405347659 0.250 Green
1/0 - 55 405348210 0.375 Pink
- 1/0 10 405477717 0.375 Black
2/0 - 10 405477717 0.375 Black
- 2/0 17 405347790 0.375 Orange
4/0 - 58 405348244 0.375 Purple
- 4/0 78 406021741 0.375 Yellow

Table of Contents