Guided Wave Radar
Level Transmitter
Enhanced Model 705
Software v3.x
Installation and Operating Manual
for use in the Hygienic Industries
ASME BPE

Table of Contents

Questions and Answers

  • C
    Carolyn FisherSep 7, 2025
    What does the 'Flooded?' message mean on Magnetrol eclipse Enhanced Model 705 Transmitter?
    • X
      xmillerSep 7, 2025
      The 'Flooded?' message indicates a loss of level signal, possibly due to flooding (twin rod probes only). Decrease the level in the vessel and set the transmitter to a lower dielectric range.
  • E
    Erin TateAug 22, 2025
    How to fix inaccurate LEVEL, % OUTPUT, and LOOP values on Magnetrol eclipse Enhanced Model 705?
    • J
      Jordan RichardsAug 22, 2025
      If the LEVEL, % OUTPUT, and LOOP values are all inaccurate, the basic configuration data might be questionable. Try reconfiguring the Probe Model, Probe Mount, Probe Length, or Level Offset. Also, ensure the Level is accurate and verify the 4 mA and 20 mA Loop values.
  • T
    Tiffany SimpsonSep 4, 2025
    Why is LEVEL reading high when it should be zero on Magnetrol eclipse Enhanced Model 705?
    • R
      Rhonda JenningsSep 5, 2025
      If the LEVEL value is reading high when it should be zero, the transmitter might be loose or disconnected from the probe. Ensure the transmitter is securely connected.
  • M
    Mrs. Jasmin ZhangSep 3, 2025
    How to resolve WeakSgnl error on Magnetrol Transmitter?
    • J
      Jessica GarciaSep 3, 2025
      If you are getting a WeakSgnl error, the signal amplitude is lower than desired. Set the transmitter to a lower dielectric range and increase the sensitivity.
  • D
    David Jones IISep 2, 2025
    What does it mean when EOP is less than probe length on Magnetrol eclipse Enhanced Model 705?
    • J
      Joshua RichardsSep 2, 2025
      If the EOP (End of Probe) is less than the Probe Length, the End of Probe signal from a dry probe is out of range. Ensure the probe length is entered correctly. Also, set the transmitter to a lower dielectric range and ensure proper blocking distance.
  • R
    Ronald StevensAug 31, 2025
    What to do if LEVEL reading is correct but LOOP is stuck at 4 mA on Magnetrol eclipse Enhanced Model 705 Transmitter?
    • B
      blackburncameronAug 31, 2025
      If the LEVEL reading on the Display is correct, but the LOOP is stuck on 4 mA, the basic configuration data might be questionable. Set the POLL ADR to 0 if you are not using HART multi-drop.
  • M
    mckaynicoleAug 30, 2025
    How to fix LEVEL, % OUTPUT, and LOOP values at maximum on Magnetrol eclipse Enhanced Model 705?
    • M
      Margaret HowellAug 30, 2025
      If the LEVEL, % OUTPUT, and LOOP values are all at the maximum level, there might be a configuration issue with the single rod probe. Increase the Blocking Distance and increase the Dielectric Range.
  • Z
    Zachary JohnstonAug 29, 2025
    Why are LEVEL, % OUTPUT, and LOOP values reading low on Magnetrol eclipse Enhanced Model 705 Transmitter?
    • A
      Allison VegaAug 29, 2025
      If the LEVEL, % OUTPUT, and LOOP values are all reading low compared to the actual level, it could be due to a lower dielectric material over a higher dielectric material, such as foam over water. Try adjusting the Threshold settings.
  • L
    Leslie PetersonAug 27, 2025
    What causes high LEVEL, % OUTPUT, and LOOP readings on Magnetrol eclipse Enhanced Model 705 Transmitter?
    • G
      Gary ThompsonAug 27, 2025
      If the LEVEL, % OUTPUT, and LOOP values are all reading high compared to the actual level, there might be an obstruction in the tank affecting the single rod probe. Adjust the sensitivity until the obstruction is ignored, or relocate the probe away from the obstruction.
  • J
    justinjimenezAug 27, 2025
    How to correct consistently high or low LEVEL readings on Magnetrol eclipse Enhanced Model 705 Transmitter?
    • M
      Michele SmithAug 27, 2025
      If LEVEL readings are repeatable but consistently high or low from the actual level by a fixed amount, the configuration data might not accurately match the probe length or tank height. Ensure the proper Probe Model and probe length are set. You can also adjust the trim level value by the amount of noted inaccuracy.

Magnetrol eclipse Enhanced Model 705 Specifications

General IconGeneral
TypeGuided Wave Radar Level Transmitter
ApplicationLevel Measurement
Measurement RangeUp to 30 m
Accuracy± 3 mm (0.12 inch)
Output Signal4-20 mA HART
Power Supply12 to 42 VDC
Process Temperature-196 to 400°C (-320 to 752°F)
Process PressureUp to 40 bar (580 psi)
ApprovalsATEX, IECEx, FM, CSA
Communication ProtocolHART
Enclosure RatingIP66/67, NEMA 4X
Material316L Stainless Steel, Hastelloy C-276
CommunicationHART
Process ConnectionThreaded, flanged