Page 60
Outputs and Inputs
thermoMETER CTL
Wiring
CAN Bus:
CAN_H on terminal „H“
CAN_L on terminal „L“
Analog signal:
Black cord on terminal „GND“
Red cord on terminal „OUT-mV“
The controller contains additional terminals to connect other devices (power supply, CAN bus, terminating
resistor).
CAN module factory settings
Module address: 20 (14 H)
Baud rate: 250 kBaud
Analog input: 0 … 10 V
Temperature range: 0 … 60 °C (2 decimal places)
Emission ratio: 0.970
i
The settings for “Analog output 0 … 10 V“ and “Temperature range 0 … 60 °C” on the CTL sensor must
be identical with the CAN bus module values.
Factory settings address and baud rate
CAN open service „LSS / Layer Setting Services“
Index temperature value:
The temperature information is located in the object register 7130h (Sub01):
e.g. B4: LB
B4: DA
B5: HB
B5: 07 T = 20.10 °C
Before delivery, MICRO-EPSILON can set parameters, desired by the customer, for an extra charge. For the
subsequent conversion a CAN master is required.