10 TEST FUNCTION
10.1 External Input/Output Forced On/Off Function
151
10
Devices that allow forced on/off registration
The following lists the devices that allow forced on/off registration.
Number of device points that allows forced on/off registration
A maximum of 32 points can be registered for input devices and output devices in total.
Inputs/outputs for which forced on/off can be set
The following describes the inputs/outputs for which forced on/off can be set.
Input
After the refreshed data from the module is reflected, the input devices for which forced on/off registration is set are forcibly
turned on or off.
Output
The following external outputs are turned on or off by refreshing output devices that have been forcibly turned on or off.
*1
Refresh target output of modules mounted on the base unit
Link refresh target output of network modules
Link refresh target output of CC-Link IE Field Network Basic
*1 When no modules are mounted on the base unit (no refresh targets), no data is output to the external outputs.
Device Range
Input R00CPU, R01CPU, and R02CPU: X0 to X1FFF (8192 points)
Other CPU modules: X0 to X2FFF (12288 points)
Output R00CPU, R01CPU, and R02CPU: Y0 to Y1FFF (8192 points)
Other CPU modules: Y0 to Y2FFF (12288 points)