10  TEST FUNCTION
10.1  External Input/Output Forced On/Off Function
151
10
Devices that allow forced on/off registration
The following lists the devices that allow forced on/off registration.
Number of device points that allows forced on/off registration
A maximum of 32 points can be registered for input devices and output devices in total.
Inputs/outputs for which forced on/off can be set
The following describes the inputs/outputs for which forced on/off can be set.
■Input
After the refreshed data from the module is reflected, the input devices for which forced on/off registration is set are forcibly 
turned on or off.
■Output
The following external outputs are turned on or off by refreshing output devices that have been forcibly turned on or off.
*1
 • Refresh target output of modules mounted on the base unit
 • Link refresh target output of network modules
 • Link refresh target output of CC-Link IE Field Network Basic
*1 When no modules are mounted on the base unit (no refresh targets), no data is output to the external outputs.
Device Range
Input • R00CPU, R01CPU, and R02CPU: X0 to X1FFF (8192 points)
• Other CPU modules: X0 to X2FFF (12288 points)
Output • R00CPU, R01CPU, and R02CPU: Y0 to Y1FFF (8192 points)
• Other CPU modules: Y0 to Y2FFF (12288 points)