27 PROCEDURE FOR STARTING UP A REDUNDANT SYSTEM
27.6 Writing Data to the Programmable Controller
433
27
27.6 Writing Data to the Programmable Controller
Write the set parameters and created programs to the CPU module.
[Online] [Write to PLC]
Operating procedure
*1 When one of both systems is started up first, the window asking for writing the data to only the connected system appears.
The same data can be written to both systems when the operation mode is the backup mode. Always write
the same data to both systems to prevent the occurrence of a file mismatch in the system consistency
check. When writing programs, FB files, or global label setting after performing [Convert] or [Rebuild All],
always write them to both systems. Otherwise, a file mismatch will be detected.
To operate CPU modules, write system parameters, CPU parameters, and program files. To operate I/O
modules and intelligent function modules, write module parameters or module extension parameters.
When new parameters have been set or the set parameters have been changed, reset the CPU module.
( MELSEC iQ-R CPU Module User's Manual (Startup))
Use the [Select Favorites] button to register frequently used items such as system parameters, CPU
parameters and programs. Select [Setting] [Register Favorites Selection] from the menu on the "Online
Data Operation" window and set the items for the [Select Favorites] button.
1. Select system parameters, CPU parameters, module
parameters, and program files on the "Online Data
Operation" window. When FBs are used, select the
corresponding FB/FUN files.
2. Click the [Execute] button.
3. When the Process CPU is not in the redundant mode,
the window shown on the left appears. Click the [Yes]
button.
4. Click the [Yes] button.
*1
5. When writing the data to the programmable controller is
completed, click the [Close] button.