The following is the list of special relay areas relating to the online module change function.
No. Name Data stored Details Set by (setting timing) CPU
SM1600 Module selection request 
flag
OffOn:Requested This relay is turned on to select an online 
change target module. When changing a 
module directly, the system turns on this 
relay upon removal of the target module. 
The relay can be turned on only when the 
value set in SD1617 is 0 (Normal operation). 
The relay turns off upon completion of the 
online module change processing. If the 
selection cancel is requested, the relay 
turns off after the selection is cancelled.
S (Status change)/U 
(Request)
RnP
RnPSF
SM1601 Module selection 
completion flag
Off: No module selected
On: Selected
This relay turns on when an online change 
target module has been selected. The relay 
turns off upon completion of the online 
module change processing.
S (Status change) RnP
RnPSF
SM1602 Module removal request 
flag
OffOn:Requested This relay is turned on to request a removal 
of the selected module. When changing a 
module directly, the system turns on this 
relay upon removal of the target module. 
The relay can be turned on only when the 
value set in SD1617 is 2 (Module selected). 
The relay turns off upon completion of the 
online module change processing.
S (Status change)/U 
(Request)
RnP
RnPSF
SM1603 Module removal ready flag Off: Not prepared
On: Ready
This relay turns on when the selected 
module is ready to be removed. The relay 
turns off upon completion of the online 
module change processing.
S (Status change) RnP
RnPSF
SM1604 Module removal completion 
flag
Off: Not completed
On: Completed
This relay turns on when the selected 
module has been removed. The relay turns 
off upon completion of the online module 
change processing.
S (Status change) RnP
RnPSF
SM1605 Module mounting 
completion flag
Off: Not completed
On: Completed
This relay turns on when a new module has 
been mounted. The relay turns off upon 
completion of the online module change 
processing.
S (Status change) RnP
RnPSF
SM1606 Module recognition request 
flag
OffOn:Requested This relay is turned on to request 
recognition of the newly-mounted module. 
When changing a module directly, the 
system turns on this relay upon mounting of 
the module. The relay can be turned on only 
when the value set in SD1617 is 6 (Module 
mounted). The relay turns off upon 
completion of the online module change 
processing.
S (Status change)/U 
(Request)
RnP
RnPSF
SM1607 Module recognition 
completion flag
Off: Not recognized
On: Recognized
This relay turns on when the newly-mounted 
module is recognized by the system. The 
relay turns off upon completion of the online 
module change processing.
S (Status change) RnP
RnPSF
SM1608 Module control resumption 
request flag
OffOn:Requested This relay turns on to start control of the 
replaced module. When changing a module 
directly, the system turns on this relay upon 
recognition of the module. The relay can be 
turned on only when the value set in 
SD1617 is 8 (Module recognized). The relay 
turns off upon completion of the online 
module change processing.
S (Status change)/U 
(Request)
RnP
RnPSF
S
M1609 Online module change 
completion flag
Off: Not completed
On: Completed
The relay turns on upon completion of the 
online module change processing. This 
relay turns off in the next scan.
S (Status change) RnP
RnPSF
SM1615 Module selection 
cancellation request flag
OffOn:Module selection 
cancellation requested
This relay is turned on to cancel a module 
selection request. The relay can be turned 
on only when the value set in SD1617 is 2 
(Module selected). The relay turns off after 
the selection is cancelled.
S (Status change)/U 
(Request)
RnP
RnPSF