290
16 MULTIPLE CPU SYSTEM FUNCTION
16.1 Out-of-group I/O Fetch
Out-of-group I/O fetch setting
In this menu item, whether or not out-of-group I/O status is fetched can be specified.
[System Parameter] [Multiple CPU Setting] [Other PLC Control Module Setting] [I/O Setting Outside Group]
Fetching input (X)
When "Import" is selected for "Input Status Outside Group" in "I/O Setting Outside Group", the input refresh before the start of
the program operation fetches On/Off data from the input module and/or intelligent function module controlled by other CPU
modules.
■Modules from which input (X) can be fetched
Input (X) can be fetched from the following modules mounted on the base/extension base unit.
• Input module
• I/O combined module
*1
• Intelligent function module
*1 Data in the areas assigned to the output portion (area not used) are not fetched. On/Off state is maintained.
Input (X) cannot be fetched from the Q series modules.
Fetching output (Y)
When "Import" is selected for "Output Status Outside Group" in "I/O Setting Outside Group", the output refresh before the start
of the program operation fetches On/Off data output to the output module and/or intelligent function module controlled by
other CPU modules into output (Y) for the host CPU module.
■Modules from which output (Y) can be fetched
Output (Y) can be fetched from the following modules mounted on the base/extension base unit.
• Output module
• I/O combined module
• Intelligent function module
Output (Y) cannot be fetched from the Q series modules.
Item Description Setting range Default
Input Status Outside Group Specify whether or not out-of-group input status is fetched. • Not Imported
• Import
Not Imported
Output Status Outside Group Specify whether or not out-of-group output status is fetched. • Not Imported
• Import
Not Imported