APPX
Appendix 1 Error Codes
737
A
3010H Data restoration
function
execution error
The model of the restoration target
CPU module differs from the
model of the backup source CPU
module.
Stop Execute the data restoration function to
the CPU module whose model is the
same as that of the backup source
CPU module.
Turn off bit 0 of SD955 to disable the
automatic data restoration function.
CPU module
data backup/
restoration
folder
information
At power-on,
at RESET
3011H Data restoration
function
execution error
Reading of backup data from an
SD memory card completed with
an error.
Stop Replace an SD memory card, and
execute the function again.
The backup data may have been
corrupted. Execute the data restoration
function using another backup data.
Turn off bit 0 of SD955 to disable the
automatic data restoration function.
CPU module
data backup/
restoration
folder
information,
drive/file
information
At power-on,
at RESET
3012H Data restoration
function
execution error
Writing of backup data to the CPU
built-in memory completed with an
error.
Stop The possible cause is a hardware
failure of the restoration target CPU
module. Execute the data restoration
function to another CPU module.
CPU module
data backup/
restoration
folder
information,
drive/file
information
At power-on,
at RESET
3013H Data restoration
function
execution error
The system file does not exist in
the backup data to be restored.
File(s) in the system file
information does not exist in the
folder of the backed up data.
Stop The backup data may have been
corrupted. Execute the data restoration
function using another backup data.
Turn off bit 0 of SD955 to disable the
automatic data restoration function.
CPU module
data backup/
restoration
folder
information
At power-on,
at RESET
3014H Data restoration
function
execution error
Data was restored to the CPU
module where the same data with
a file password has already been
stored.
Stop Delete file passwords, and execute the
CPU module data backup/restoration
function.
Turn off bit 0 of SD955 to disable the
automatic data restoration function.
CPU module
data backup/
restoration
folder
information
At power-on,
at RESET
3015H Data restoration
function
execution error
A folder with a value that matches
the restoration target date folder
setting value or number folder
setting value does not exist in the
SD memory card.
The restoration target data setting
value is out of range.
The restoration target date folder
setting value or number folder
setting value is out of range.
Stop Check and correct the restoration
target date folder setting value or
number folder setting value, and
execute the function again.
Check and correct the restoration
target data setting value, and execute
the function again.
Turn off bit 0 of SD955 to disable the
automatic data restoration function.
CPU module
data backup/
restoration
folder
information
At power-on,
at RESET
3016H Data restoration
function
execution error
The automatic data restoration
function was executed with the
CPU module where an SD
memory card was not inserted.
Stop Insert or re-insert an SD memory card,
and execute the function again.
Turn off bit 0 of SD955 to disable the
automatic data restoration function.
CPU module
data backup/
restoration
folder
information
At power-on,
at RESET
3017H Data restoration
function
execution error
The automatic data restoration
function was executed exceeding
the maximum memory capacity of
the CPU module.
The automatic data restoration
function was executed exceeding
the maximum number of files that
can be stored in the CPU module.
Stop Execute the function so that the
maximum memory capacity will not be
exceeded.
Execute the function so that the
maximum number of storable files will
not be exceeded.
Turn off bit 0 of SD955 to disable the
automatic data restoration function.
CPU module
data backup/
restoration
folder
information
At power-on,
at RESET
3018H Data restoration
function
execution error
The status (such as programs,
parameters, and file structure) of
the CPU module differs from that
of when the data backup function
was executed.
Stop Match the CPU module status to the
one at the time of backup, and execute
the function again.
Set all data as the backup/restoration
target data, and execute the data
restoration function.
Turn off bit 0 of SD955 to disable the
automatic data restoration function.
CPU module
data backup/
restoration
folder
information
At power-on,
at RESET
3070H Operation stop
error
The PABORT instruction was
executed.
Stop Check the detailed information (error
location information) of the error by
executing module diagnostics using
the engineering tool and check the
corresponding program - one that
outputs the program error code.
Error location
information
and program
error
information
At instruction
execution
Error
code
Error name Error details and cause Stop/
continue
Action Detailed
information
Diagnostic
timing