APPX
Appendix 1 Error Codes
737
A
3010H Data restoration
function
execution error
• The model of the restoration target
CPU module differs from the
model of the backup source CPU
module.
Stop • Execute the data restoration function to
the CPU module whose model is the
same as that of the backup source
CPU module.
• Turn off bit 0 of SD955 to disable the
automatic data restoration function.
CPU module
data backup/
restoration
folder
information
At power-on,
at RESET
3011H Data restoration
function
execution error
• Reading of backup data from an
SD memory card completed with
an error.
Stop • Replace an SD memory card, and
execute the function again.
• The backup data may have been
corrupted. Execute the data restoration
function using another backup data.
• Turn off bit 0 of SD955 to disable the
automatic data restoration function.
CPU module
data backup/
restoration
folder
information,
drive/file
information
At power-on,
at RESET
3012H Data restoration
function
execution error
• Writing of backup data to the CPU
built-in memory completed with an
error.
Stop • The possible cause is a hardware
failure of the restoration target CPU
module. Execute the data restoration
function to another CPU module.
CPU module
data backup/
restoration
folder
information,
drive/file
information
At power-on,
at RESET
3013H Data restoration
function
execution error
• The system file does not exist in
the backup data to be restored.
• File(s) in the system file
information does not exist in the
folder of the backed up data.
Stop • The backup data may have been
corrupted. Execute the data restoration
function using another backup data.
• Turn off bit 0 of SD955 to disable the
automatic data restoration function.
CPU module
data backup/
restoration
folder
information
At power-on,
at RESET
3014H Data restoration
function
execution error
• Data was restored to the CPU
module where the same data with
a file password has already been
stored.
Stop • Delete file passwords, and execute the
CPU module data backup/restoration
function.
• Turn off bit 0 of SD955 to disable the
automatic data restoration function.
CPU module
data backup/
restoration
folder
information
At power-on,
at RESET
3015H Data restoration
function
execution error
• A folder with a value that matches
the restoration target date folder
setting value or number folder
setting value does not exist in the
SD memory card.
• The restoration target data setting
value is out of range.
• The restoration target date folder
setting value or number folder
setting value is out of range.
Stop • Check and correct the restoration
target date folder setting value or
number folder setting value, and
execute the function again.
• Check and correct the restoration
target data setting value, and execute
the function again.
•
Turn off bit 0 of SD955 to disable the
automatic data restoration function.
CPU module
data backup/
restoration
folder
information
At power-on,
at RESET
3016H Data restoration
function
execution error
• The automatic data restoration
function was executed with the
CPU module where an SD
memory card was not inserted.
Stop • Insert or re-insert an SD memory card,
and execute the function again.
• Turn off bit 0 of SD955 to disable the
automatic data restoration function.
CPU module
data backup/
restoration
folder
information
At power-on,
at RESET
3017H Data restoration
function
execution error
• The automatic data restoration
function was executed exceeding
the maximum memory capacity of
the CPU module.
• The automatic data restoration
function was executed exceeding
the maximum number of files that
can be stored in the CPU module.
Stop • Execute the function so that the
maximum memory capacity will not be
exceeded.
• Execute the function so that the
maximum number of storable files will
not be exceeded.
• Turn off bit 0 of SD955 to disable the
automatic data restoration function.
CPU module
data backup/
restoration
folder
information
At power-on,
at RESET
3018H Data restoration
function
execution error
• The status (such as programs,
parameters, and file structure) of
the CPU module differs from that
of when the data backup function
was executed.
Stop • Match the CPU module status to the
one at the time of backup, and execute
the function again.
• Set all data as the backup/restoration
target data, and execute the data
restoration function.
• Turn off bit 0 of SD955 to disable the
automatic data restoration function.
CPU module
data backup/
restoration
folder
information
At power-on,
at RESET
3070H Operation stop
error
• The PABORT instruction was
executed.
Stop • Check the detailed information (error
location information) of the error by
executing module diagnostics using
the engineering tool and check the
corresponding program - one that
outputs the program error code.
Error location
information
and program
error
information
At instruction
execution
Error
code
Error name Error details and cause Stop/
continue
Action Detailed
information
Diagnostic
timing