APPX
Appendix 9 Processing Time
899
A
Overhead time when executing the interrupt program
The overhead time when executing the interrupt program includes the one before executing the interrupt program and the
other when the interrupt program finished.
Overhead time before executing the interrupt program
Overhead time when finishing the interrupt program
Overhead time when executing the fixed scan execution type program
The following table lists the overhead times when executing the fixed scan execution type program.
Interrupt factor Condition Overhead time
Internal timer interrupt (I28 to I31) Saves/stores the file register (R) block number. 19.5s
Not save/store the file register (R) block number. 12.9s
Inter-module synchronous interrupt (I44) Saves/stores the file register (R) block number. 25.4s
Not save/store the file register (R) block number. 17.0s
Multiple CPU synchronous interrupt (I45) Saves/stores the file register (R) block number. 24.2s
Not save/store the file register (R) block number. 16.1s
High-speed internal timer interrupt 2 (I48), high-speed internal
timer interrupt 1 (I49)
Saves/stores the file register (R) block number. 25.8s
Not save/store the file register (R) block number. 18.1s
Interrupt from module (I0 to I15, I50 to I1023) Saves/stores the file register (R) block number. 19.1s
Not save/store the file register (R) block number. 12.8s
Interrupt factor Condition Overhead time
Internal timer interrupt (I28 to I31) Saves/stores the file register (R) block number. 16.0s
Not save/store the file register (R) block number. 8.5s
Inter-module synchronous interrupt (I44) Saves/stores the file register (R) block number. 19.0s
Not save/store the file register (R) block number. 11.4s
Multiple CPU synchronous interrupt (I45) Saves/stores the file register (R) block number. 18.7s
Not save/store the file register (R) block number. 10.5s
High-speed internal timer interrupt 2 (I48), high-speed internal
timer interrupt 1 (I49)
Saves/stores the file register (R) block number. 19.4s
Not save/store the file register (R) block number. 10.3s
Interrupt from module (I0 to I15, I50 to I1023) Saves/stores the file register (R) block number. 15.7s
Not save/store the file register (R) block number. 8.5s
Condition Overhead time
Saves/stores the file register (R) block number. 37.9s
Not save/store the file register (R) block number. 20.6s