APPX
Appendix 13  How to Use CPU Module Logging Configuration Tool
957
A
 • Details of each data
No. Item Description Size (byte)
(1) Identification code When the version of CPU Module Logging Configuration Tool is "1.82L" or later and local devices or 
labels are specified, "MRDB" is always output to identify the file.
When the version of CPU Module Logging Configuration Tool is "1.76E" or earlier, or the version is 
"1.82L" or later and only global devices are specified, "MRCB" is always output to identify the file.
4
(2) File version When the version of CPU Module Logging Configuration Tool is "1.82L" or later and local devices or 
labels are specified, file version 2 is displayed.
When the version of CPU Module Logging Configuration Tool is "1.76E" or earlier, or the version is 
"1.82L" or later and only global devices are specified, file version 1 is displayed.
1
(3) File type The file type is output. (fixed to 1: Continuous/trigger logging) 1
(4) Model information The module model name that outputted binary file is output. RCPU is output to the first eight bytes 
and 00H is output to the last eight bytes.
*1
16
(5) Added-data 
information
The output selection setting for the data that can be output is output.
b0 1: Output date and time data.
0: Do not output date and time data.
b1 1: Output a data collection interval.
0: Do not output a data collection interval.
b2 1: Output an execution step No.
0: Do not output an execution step No.
b3 1: Output an execution program name and No.
0: Do not output an execution program name or No.
b4 1: Output a trigger flag.
0: Do not output a trigger flag.
b5 1: Output index.
0: Do not output index.
b6 1: Output device comments.
0: Do not output device comments.
b7 1: Output comments.
0: Do not output comments.
b9 1: Output device comments for each program.
0: Do not output device comments for each program.
2
(6) Comment size The comment length of (7) Comment is output. 2
(7) Comment The comment specified in the setting is output in Unicode. 2 to 512
(8) Number of collected 
data
The number of data points of the data information ((9) to (17) and (29) to (31)) for data logging is output. 2
(9) Data information size The total size of the data information ((9) to (17) and (29) to (31)) for data logging is output. 2
(10) Data type The numeric value shown below is output depending on the data type.
0000H: Bit
0001H: Word (signed)
0002H: Double word (unsigned)
0003H: Word (signed)
0004H: Double word (unsigned)
0005H: Single-precision real number
0006H: Double-precision real number
0007H: String
0008H: Numeric string
0009H: Time
2
(11) Output type The same numerical value as the value in (10) Data type is output. However, when the data type is bit, 
character string, numeric string, or time, FFFFH is output because the output type cannot be specified.
2
(12) Data information 
setting
The data-related information is output.
b2 1: Device comment specified
0: Device comment not specified
b3 1: Device code specified
0: Device code not specified
b4 1: Program name length/program name specified
0: Program name length/program name not specified
2
(13) Data length The data length of data is output. When the data type is the bit type, it will be output as two bytes. 2
(14) Data name length The length of the data name specified in the setting is output. 2
(15) Data name The data name specified in the setting is output in Unicode. 2 to 512
b9 b7 b6 b5 b4 b3 b2 b1 b0