37 FUNCTIONS
37.4 System Consistency Check
643
37
Execution timing
The following table shows the execution timing of the system consistency check.
*1 Checking this item can be disabled by setting "Backup Mode Setting" of "Redundant Behavior Setting". ( Page 652 Redundant
System Operation Setting)
In the following conditions, the system consistency check is not performed.
One of the systems has not started up. (The CPU module is powered off or is reset or during an initial processing.)
A stop error has occurred in the CPU module.
The memory copy is being executed.
Item Execution timing
File When both systems are simultaneously turned on or reset
When one system is turned on or reset while waiting for the start-up of the other system
When the standby system is turned on or reset while the control system is operating
When the operating status of the CPU module is switched from STOP to RUN
At END processing
At online change completion
At system switching
When a tracking cable is reconnected
Operating status
*1
When the standby system is turned on or reset while the control system is operating
When the operating status of the CPU module is switched from STOP to RUN
At END processing
When a tracking cable is reconnected
Mounting status of main base unit When both systems are simultaneously turned on or reset
When one system is turned on or reset while waiting for the start-up of the other system
When the standby system is turned on or reset while the control system is operating
When a tracking cable is reconnected
SD memory card When both systems are simultaneously turned on or reset
When one system is turned on or reset while waiting for the start-up of the other system
When the standby system is turned on or reset while the control system is operating
Safety operation mode
*1
When the standby system is turned on or reset while the control system is operating
When the operating status of the CPU module is switched from STOP to RUN
At END processing
When a tracking cable is reconnected