672
37 FUNCTIONS
37.16 RAS Functions
*1 If a safety communications error (minor error) occurs between safety stations, a safety station interlock will be triggered for safety
communications between relevant stations, and safety communications will not be resumed until the safety station interlock is released.
The safety station interlock is released with safety special register areas (safety station interlock release request for each safety
connection). ( Page 885 List of Safety Special Register Areas)
For details on the safety station interlock status, refer to the following.
MELSEC iQ-R CC-Link IE Field Network User's Manual (Application)
■SIL2 function module
*1 If a safety communications error (minor error) occurs between safety stations, a safety station interlock will be triggered for safety
communications between relevant stations, and safety communications will not be resumed until the safety station interlock is released.
The safety station interlock is released with safety special register areas (safety station interlock release request for each safety
connection). ( Page 885 List of Safety Special Register Areas)
For details on the safety station interlock status, refer to the following.
MELSEC iQ-R CC-Link IE Field Network User's Manual (Application)
How to clear errors
Errors in the SIL2 Process CPU can be cleared in the same way as for the standard CPU. ( Page 135 How to clear errors)
The following describes how to clear errors in the SIL2 function module. The errors in the other system cannot be cleared.
Clear the errors separately in each system.
■Using the engineering tool
Clear errors with the module diagnostics function of GX Works3. ( GX Works3 Operating Manual)
■Using the buffer memory
Clear errors using operations of buffer memory.
1. Check the standard program and identify the detected continuation error using Un\G0 (Latest self-diagnostic error code).
2. Eliminate the cause of the detected continuation error.
3. Set 1 in Un\G50 (Error clear) in the standard program to clear the error.
*1
*1 After the error is cleared, 0 is automatically set in Un\G50 by the system.
Standby system CPU module error 1B60H, 1B61H
Tracking communications disabled 1B70H
Tracking communication error 1B71H, 1B78H
Tracking transfer error 1B80H, 1B81H, 1B82H
Redundant function module error 1BA0H
System switching error 1BD0H, 1BD1H
Memory card error 2120H, 2121H
Module verification error 2400H, 2401H
Fuse blown error 2420H
Module major error 2441H, 2442H, 2450H
Another CPU module major error 2461H, 2462H, 2470H
I/O number or network number specification error 2800H, 2801H, 2802H, 2803H, 2804H, 2805H, 2806H, 2807H, 2810H
Device, label, or buffer memory specification error 2820H, 2821H, 2822H, 2823H, 2824H
File name specification error 2840H, 2841H, 2842H
Operation error 3400H, 3401H, 3402H, 3403H, 3404H, 3405H, 3406H, 3420H, 3421H,
3422H, 3423H, 3424H, 3440H, 3441H, 34A0H
Error name Error code
ROM write count error 1080H
Safety cycle time exceeded 1A00H
Destination station error in safety communications 1A40H
*1
Parameter mismatch in safety communication destination station 1A50H
*1
Device mismatch in safety communication destination station 1A51H
*1
Device version mismatch in safety communication destination station 1A52H
*1
Timeout in safety communications 1A60H
*1
, 1A61H
*1
, 1A62H
*1
, 1A63H
*1
, 1A64H
*1
, 1A65H
*1
, 1A66H
*1
, 1A80H
*1
Safety communications receipt data error 1A70H
*1
, 1A71H
*1
, 1A72H
*1
, 1A73H
*1
Error name Error code