Appendix 1 Error Codes
707
A
11A1H PID operation
error
• A value outside the range ( < 0
or 100 ) was specified for the
input filter constant ().
Continue • Check and correct the input filter
constant () value.
Error location
information
At instruction
execution
11A2H PID operation
error
• A value outside the range (K
P
< 0)
was specified for the proportional
gain (K
P
).
Continue • Check and correct the proportional
gain (K
P
) value.
Error location
information
At instruction
execution
11A3H PID operation
error
• A value outside the range (T
I
< 0)
was specified for the integral time
(T
I
).
Continue • Check and correct the integral time (T
I
)
value.
Error location
information
At instruction
execution
11A4H PID operation
error
• A value outside the range (K
D
< 0
or 201 K
D
) was specified for the
derivative gain (K
D
).
Continue • Check and correct the derivative gain
(K
D
) value.
Error location
information
At instruction
execution
11A5H PID operation
error
• A value outside the range (T
D
< 0)
was specified for the derivative
time (T
D
).
Continue • Check and correct the derivative time
(T
D
) value.
Error location
information
At instruction
execution
11A6H PID operation
error
• A value less than or equal to the
operation cycle was specified for
the sampling time (T
S
).
Continue • Check and correct the sampling time
(T
S
) value.
Error location
information
At instruction
execution
11A7H PID operation
error
• A process value variation (PV)
overflow occurred.
Continue • Check and correct the control data
setting values.
Error location
information
At instruction
execution
11A8H • A deviation (EV) overflow
occurred.
11A9H • An integral calculation value
overflow occurred.
11AAH • A derivative gain (K
D
) value
overflow occurred.
11ABH PID operation
error
• A differential calculation value
overflow occurred.
Continue • Check and correct the control data
setting values.
Error location
information
At instruction
execution
11ACH • A PID operation result overflow
occurred.
11ADH PID operation
error
• A value smaller than the output
lower limit setting value was
specified for the output upper limit
setting value.
Continue • Check and correct the output upper
limit setting value or output lower limit
setting value.
Error location
information
At instruction
execution
11AEH PID operation
error
• A value smaller than 0 was
specified for the input variation
amount warning setting value or
output variation amount warning
setting value.
Continue • Change the input variation amount
warning setting value or output
variation amount warning setting value
to a value greater than 0.
Error location
information
At instruction
execution
11AFH PID operation
error
• The deviation when starting auto
tuning (step response method)
became 150 or less.
• The deviation when finishing auto
tuning (step response method)
was 1/3 or greater than the
deviation when starting.
Continue • Check and correct the control data.
• If the deviation when starting auto
tuning (step response method) is not
150 or more, specify a set value for
auto tuning.
Error location
information
At instruction
execution
11B0H PID operation
error
• The movement direction assumed
from the relationship between the
set value and process value when
starting auto tuning (step
response method) and the output
value movement direction do not
match.
Continue • Perform auto tuning again after
correcting the relationship between the
set value, auto tuning (step response
method) output value, and process
value.
• Check and correct the control data.
Error location
information
At instruction
execution
11B1H PID operation
error
• The input value (PV) did not
change correctly, and auto tuning
(step response method) did not
function normally.
Continue • Set a long time for the sampling time
(T
S
).
• Set a larger value for the input filter
constant ().
• Check the input value (PV).
Error location
information
At instruction
execution
11B2H PID operation
error
• A value equal to or lower than the
output lower limit (LLV) was
specified for the auto tuning (limit
cycle method) output upper limit
(ULV).
Continue • Check and correct the output upper
limit (ULV) and output lower limit (LLV)
values.
Error location
information
At instruction
execution
Error
code
Error name Error details and cause Stop/
continue
Action Detailed
information
Diagnostic
timing