Appendix 1 Error Codes
1165H UDP/IP send
failed
Data was not sent correctly with
UDP/IP.
Continue Check the settings for connection with
the external device.
Check the operation of the external
device or switching hub.
Since there may be congestion of
packets on the line, send data after a
certain period of time.
Check if the Ethernet communication
load is high because of the Ethernet
functions being executed. Use the
Ethernet functions so that the
communication load is reduced.
Check if the connection cable is
disconnected.
Check that there is no connection
failure with the switching hub.
Execute a PING test. If the test
completes with an error, take an action
to correct the error.
Always
1166H TCP/IP send
failed
Data was not sent correctly with
TCP/IP.
Continue Check the settings for connection with
the external device.
Check the operation of the external
device or switching hub.
Since there may be congestion of
packets on the line, send data after a
certain period of time.
Check if the Ethernet communication
load is high because of the Ethernet
functions being executed. Use the
Ethernet functions so that the
communication load is reduced.
Check if the connection cable is
disconnected.
Check that there is no connection
failure with the switching hub.
Execute a PING test. If the test
completes with an error, take an action
to correct the error.
Always
1167H Unsend data
send error
Unsent data found, but could not
be sent.
Continue Check the settings for connection with
the external device.
Check the operation of the external
device or switching hub.
Since there may be congestion of
packets on the line, send data after a
certain period of time.
Check if the Ethernet communication
load is high because of the Ethernet
functions being executed. Use the
Ethernet functions so that the
communication load is reduced.
Check if the connection cable is
disconnected.
Check that there is no connection
failure with the switching hub.
Execute a PING test. If the test
completes with an error, take an action
to correct the error.
Always
1180H Redundant IP
address error
The same IP address has been
set as the system A IP address,
system B IP address, and/or
control system IP address
Network addresses of the system
A IP address, system B IP
address, and control system IP
address are different.
Continue Set different IP addresses for the
system A IP address, system B IP
address, and control system IP
address.
Set the same network address for the
system A IP address, system B IP
address, and control system IP
address.
Parameter
information
At power-on,
at RESET
11A0H PID operation
error
A value outside the range (T
S
0)
was specified for the sampling
time (T
S
).
Continue Check and correct the sampling time
(T
S
) value.
Error location
information
At instruction
execution
Error
code
Error name Error details and cause Stop/
continue
Action Detailed
information
Diagnostic
timing