16 REMOTE OPERATION
16.4 Remote RESET
223
16
16.4 Remote RESET
This function externally resets a CPU module in the STOP state (including that stopped due to an error). Even when the RUN/
STOP/RESET switch of a CPU module is set to RUN, the CPU module can be reset in the STOP state.
To perform the remote RESET operation when "Execution Target" of the remote operation is set to "All
Stations Specified" or "Specify Group No.", ensure that the CPU module set in "Specify Connection
Destination Connection" of the engineering tool is in the STOP state. (Even if a CPU module in the STOP
state exists on the specified network, the remote RESET does not operate.)
Enabling remote RESET
Performing remote RESET requires setting for enabling remote reset.
[CPU Parameter] [Operation Related Setting] [Remote Reset Setting]
Window
Displayed items
Item Description Setting range Default
Remote RESET Set whether or not to enable the remote RESET. Disable
Enable
Disable