27 DEVICES
27.5 Link Direct Device
471
27
27.5 Link Direct Device
This device directly accesses link relays and/or link registers of the network module in the CC-Link IE Controller Network and/
or CC-Link IE Field Network.
Specification method
Specify a link direct device as shown below: The link register 10 (W10) of the network number 2 can be specified as "J2\W10".
For bit devices, digit specification is allowed. (Example: J1\K1X0, J10\K4B0)
Device No.
• Input
• Output
• Link relay
• Link register
• Link special relay
• Link special register From SW0
Network No.1 to 239
Specification method: J\
From SB0
From W0
B0
From Y0
From X0