27 DEVICES
27.12 Pointer (P)
Pointer setting
The following menu item is to set pointers.
[CPU Parameter] [Memory/Device Setting] [Pointer Setting]
Window
Displayed items
*1 Up to the number of "Total points of pointer device area" - "Number of points of global pointer".
*2 The default number of points is 32768 for the R120PCPU.
*3 The default number of points is 8192 for the R120PCPU.
*4 The default number of points is 16384 for the R120PCPU.
Specify a pointer number which is equal to or lower than "(end number of the pointer range specified in the
parameter) - (number of points of the global pointers)".
Item Description Setting range Default
Global Pointer Start Set the start number of the global pointer. P0 and over
*1
0
Total Points Check the total number of points for the pointer. 16384 points
*2
Global Pointer Set the number of points of the global pointer. R120PCPU: 0 to 32768 points (in increments
of 1 point)
Other CPU modules: 0 to 16384 points (in
increments of 1 point)
4096 points
*3
Local Pointer Set the number of points of the local pointer. 4096 points
*3
Pointer Type Label Set the number of points for the pointer type label
assignment area.
8192 points
*4