20 DATA LOGGING FUNCTION
20.11 Auto Logging
291
20
Auto logging common setting
The following window configures the required settings for using the auto logging function.
Window
Displayed items
Item Description Setting range Default
Enable the auto logging function Select this item to use auto logging. Not checked
Auto logging
terminate
condition
Data logging stop Select the condition to complete the auto logging
operation. ( Page 292 Conditions for auto
logging completion)
When all data loggings
stop
When any of the data
loggings stops
When all data
loggings stop
Timer Complete with
timer
Select this checkbox to stop the auto logging
operation by a timer.

Elapsed time Specify the time interval from the start of the data
logging until stopping it.
1 to 86400 seconds