26 REDUNDANT FUNCTION
26.2 System Switching
377
26
System switching request from a network module
The network module on the main base unit of the control system requests the CPU module to switch systems when a
communication error or a disconnection is detected. (The network module on an extension base unit does not request the
CPU module to switch systems when an error is detected.)
When the CPU module of the control system receives a system switching request from the network module, the systems are
switched after the END processing.
Ex.
Operation when the CPU module receives a system switching request from a network module
When disconnecting the network cable of the control system for maintenance or other reasons, disconnect the
network cable of the standby system in advance. System switching will not occur even when the network
cable of the control system is disconnected.
The following network modules send a system switching request.
CC-Link IE Controller Network module
CC-Link IE Field Network module
Ethernet interface module with built-in CC-Link IE
MELSECNET/H network module
PROFIBUS-DP module
If a network module cable is disconnected, the systems may not be switched depending on the timing of error detection on the
control system and the timing on the standby system. ( Page 387 When the cable for the network module is
disconnected)
END
Program executed
System switching request from a network module
System A
System B
System switching
Standby system
Program stopped
Program executed
Control system
Control system
Program stopped
Standby system