35  MAINTENANCE AND INSPECTION OF A REDUNDANT SYSTEM
35.1  Module Replacement in a Redundant System
541
35
*1 When the power supply module is redundant, only one of the two power supply modules can be replaced.
*2 A module can be replaced by turning on SM1646 (System switching by a user) to execute system switching and powering off the main 
base unit in the standby system after system switching.
*3 A module supporting the online module change function can be replaced by online module change. ( MELSEC iQ-R Online Module 
Change Manual)
*4 When replacing a module not supporting the online module change function, the module can be replaced by turning on SM1646 
(System switching by a user) to execute system switching and powering off the main base unit in the standby system after system 
switching.
 • When a module is replaced after powering off the standby system, a continuation error occurs in the CPU 
module of the control system. After replacing a module, clear the continuation error that has occurred in the 
CPU module of the control system.
 • When replacing the CPU module, if functions added or changed by the upgrade are used, replace it with a 
CPU module with a firmware version that supports those functions. ( Page 747 Added and Enhanced 
Functions)
■Replacement/addition of a base unit and extension cable
The following table lists base units and extension cables, and whether they can be replaced/added.
Replacement target Availability Reference
Main base unit Main base unit of the standby 
system
Can be replaced by powering off the main base unit of the 
standby system.
Page 546 Replacing the main 
base unit
Main base unit of the control 
system
Can be replaced by turning on SM1646 (System switching by a 
user) to execute system switching and powering off the main 
base unit in the standby system after system switching.
Extension base unit The extension base unit cannot be turned off and replaced 
while the system is operating.
Extension cable Between the main base unit of 
the standby system and the 
extension base unit
Can be replaced by powering off the main base unit of the 
standby system.
Page 547 Replacing the 
extension cable between the main 
base unit and extension base unit
Between the main base unit of 
the control system and the 
extension base unit
Can be replaced by turning on SM1646 (System switching by a 
user) to execute system switching and powering off the main 
base unit in the standby system after system switching.
Between extension base units Only the inactive extension cable can be replaced. If the 
extension cable on the active side is disconnected, system 
switching occurs, and the cable cannot be replaced.
Page 547 Replacing the 
extension cable between 
extension base units