36 ERROR CODES
36.4 List of Error Codes
563
36
2040H CPU module
configuration
error
The number of CPU modules set in
the system parameters ("I/O
Assignment Setting") differs from the
number of CPU modules actually
mounted.
The CPU module is mounted on the
slot different from the one specified in
the system parameters (I/O
assignment setting).
Two or more Safety CPUs are
mounted.
Stop Correctly set the number of CPU
modules (including the empty
setting) in the system parameters
in accordance with the number of
CPU modules actually mounted.
Correctly set the system
parameters so that the setting and
actual CPU module mounting
status will be the same.
Mount only one Safety CPU.
System
configuration
information
At power-on, at
RESET
2041H CPU module
configuration
error
The CPU module is not mounted on
the slot that is set for the CPU module
in the system parameters ("I/O
Assignment Setting").
The CPU module is mounted on the
slot that is set for empty in the system
parameters ("I/O Assignment
Setting").
An I/O module or intelligent function
module is mounted between the CPU
modules.
Arrangement of CPU modules
mounted is not appropriate to
configure a multiple CPU system.
Stop Check and correct the I/O
assignment setting in the system
parameters.
Correctly set the number of CPU
modules (including the empty
setting) in the system parameters
in accordance with the number of
CPU modules actually mounted.
Remove the I/O module or
intelligent function module
mounted between the CPU
modules.
System
configuration
information
At power-on, at
RESET
2043H CPU module
configuration
error
The CPU module is mounted on the
inapplicable slot.
Stop Mount the CPU module on the
applicable slot (CPU slot or I/O
slot 0 to 6).
Remove the CPU module from the
inapplicable slot.
System
configuration
information
At power-on, at
RESET
2044H CPU module
configuration
error
The host CPU No. set in the system
parameters ("I/O Assignment
Setting") differs from the one
determined by the mounting position
of the CPU module.
Stop Re-set the host CPU No. in the
system parameters in accordance
with the mounting position of the
CPU module.
System
configuration
information
At power-on, at
RESET, at
STOP RUN
state
2046H CPU module
configuration
error
Another CPU module was accessed,
but there was no response.
Stop Check and correct the I/O
assignment setting in the system
parameters.
Take measures to reduce noise.
R
eset the CPU module and run it
again. If the same error code is
displayed again, the possible
cause is a hardware failure of
another CPU module. Please
consult your local Mitsubishi
representative.
System
configuration
information
Always
2050H CPU module
configuration
error
An unsupported CPU module is
mounted.
Stop Remove the unsupported CPU
module. If all the CPU modules
are supported, the possible cause
is a hardware failure of the CPU
module or base unit. Please
consult your local Mitsubishi
representative.
System
configuration
information
At power-on, at
RESET
2051H CPU module
configuration
error
A CPU module that does not support
the online module change (direct
change) function is used in a multiple
CPU system.
Stop Refer to the MELSEC iQ-R Online
Module Change Manual, and
correct the system configuration.
To disable the online module
change (direct change) function,
set "Direct change setting" to
"Disable" in the CPU parameters.
If the same error code is displayed
again, the possible cause is a
hardware failure of the CPU
module or base unit. Please
consult your local Mitsubishi
representative.
System
configuration
information
At power-on, at
RESET
Error
code
Error name Error details and cause Stop/
continue
Action Detailed
information
Diagnostic
timing