36 ERROR CODES
36.4 List of Error Codes
565
36
2101H Memory error An extended SRAM cassette is
inserted or removed while the
programmable controller is powered
on.
Stop Do not insert or remove an
extended SRAM cassette during
operation.
Check the mounting status of the
CPU module of the extended
SRAM cassette. If the same error
code is displayed again, the
possible cause is a hardware
failure of the extended SRAM
cassette. Please consult your local
Mitsubishi representative.
Drive/file
information
Always
2102H Memory error An error has been detected in the
inserted extended SRAM cassette.
Stop Check the mounting status of the
CPU module of the extended
SRAM cassette. If the same error
code is displayed again, the
possible cause is a hardware
failure of the extended SRAM
cassette or CPU module. Please
consult your local Mitsubishi
representative.
Drive/file
information
Always
2103H Memory error An unsupported extended SRAM
cassette is mounted.
Stop Replace the extended SRAM
cassette with the one supported
by the CPU module.
Drive/file
information
Always
2120H Memory card
error
The memory card was removed
without the card being disabled.
Stop/
continue
Disable the memory card, and
then remove it.
Drive/file
information
Always
2121H Memory card
error
An error has been detected in the
memory card.
Stop/
continue
Format the memory card, re-insert
the memory card, or replace the
memory card. If the same error
code is displayed again, the
possible cause is a hardware
failure of the CPU module. Please
consult your local Mitsubishi
representative.
Drive/file
information
Always
2122H Memory card
error
The CPU module did not start
because the memory card was not
restored during the startup
processing.
Stop Reset the CPU module. If the
same error code is displayed
again, the possible cause is a
hardware failure of the memory
card. Replace the memory card.
Drive/file
information
At power-on, at
RESET
2150H Initial
processing time
error
Since the initial processing takes time,
the host CPU in a multiple CPU
system cannot respond to
communication requests from other
CPU modules in initial
communications. (Other CPU
modules cannot start up.)
Stop Take the following action to shorten
the initial processing time.
Check and correct the restoration
setting and the number of files to
be restored if the automatic data
restoration function is being
executed.
At power-on, at
RESET
2160H IP address
duplication error
Overlapping IP addresses have been
detected.
Stop Check and correct the IP
addresses.
Always
2180H Invalid file An invalid file has been detected. Stop Check the detailed information
(drive/file information) of the error
by executing module diagnostics
u
s
ing the engineering tool, select
the correct file name, and write the
specified file to the CPU module. If
the same error code is displayed
again, the possible cause is a
hardware failure of the CPU
module. Please consult your local
Mitsubishi representative.
Drive/file
information
At power-on, at
RESET, at
STOP RUN
state
2181H Invalid file Due to firmware update or restoration
(after the firmware update) of the CPU
module, a program file of which file
structure is not supported by the new
version of the firmware or the
operation mode of the CPU module
has been written.
Stop After reading program files from
the programmable controller,
format the memory and write the
program files. Then, reset the
CPU module and run it again.
Drive/file
information
At power-on, at
RESET
2182H Invalid file The program file is incorrect. Or, the
program file is not written properly.
Stop Write the program file to the CPU
built-in memory again.
Drive/file
information
At power-on, at
RESET
Error
code
Error name Error details and cause Stop/
continue
Action Detailed
information
Diagnostic
timing

Table of Contents