36 ERROR CODES
36.4 List of Error Codes
569
36
2260H Parameter error
(network)
• Network numbers are overlapping. Stop • Check the detailed information
(parameter information) of the
error by executing module
diagnostics using the engineering
tool and correct the parameter
setting corresponding to the
displayed number. If the same
error code is displayed again, the
possible cause is a hardware
failure of the data memory in the
CPU module or the intelligent
function module connected.
Please consult your local
Mitsubishi representative.
Parameter
information
At power-on, at
RESET
2261H Parameter error
(network)
• Different network types (CC IE
Control extended mode/normal mode)
are set between the control station
and the normal station.
Stop • Check the detailed information
(parameter information) of the
error by executing module
diagnostics using the engineering
tool and correct the parameter
setting corresponding to the
displayed number. If the same
error code is displayed again, the
possible cause is a hardware
failure of the data memory in the
CPU module or the intelligent
function module connected.
Please consult your local
Mitsubishi representative.
Parameter
information
At power-on, at
RESET, at
STOP RUN
state
2262H Parameter error
(network)
• When the station number of the
MELSECNET/H network module is 0,
parameters of PLC to PLC network
are set.
• The station type set in the module
parameters differs from that of the
module actually mounted.
• In the CPU module in redundant
mode, "RJ71GF11-T2" (the model
name cannot be set for the redundant
system) is selected to the model
name in the I/O assignment setting of
the system parameter.
Stop • Correct the station number of the
MELSECNET/H network module.
• Check the detailed information
(parameter information) of the
error by executing module
diagnostics using the engineering
tool and correct the parameter
setting corresponding to the
displayed number.
• In the CPU module in redundant
mode, select "RJ71GF11-
T2(MR)", "RJ71GF11-T2(SR)", or
"RJ71GF11-T2(LR)" (model
names can be set for the
redundant system) to the model
name in the I/O assignment
setting of the system parameter.
If the same error code is displayed
again, the possible cause is a
hardware failure of the data memory
in the CPU module or the intelligent
function module connected. Please
consult your local Mitsubishi
representative.
Parameter
information
At power-on, at
RESET, at
STOP RUN
state
2263H Parameter error
(network)
• Even though the CC-Link IE module
or MELSECNET/H network module is
mounted, a different CC-Link IE
module or MELSECNET/H network
module is set in the system
parameters ("I/O Assignment
Setting"), or CC-Link IE module or
MELSECNET/H network module
parameters have not been set.
Stop • Set the system parameters and
module parameters. If the same
error code is displayed again, the
possible cause is a hardware
failure of the data memory in the
CPU module or the intelligent
function module connected.
Please consult your local
Mitsubishi representative.
Parameter
information
At power-on, at
RESET, at
STOP RUN
state
Error
code
Error name Error details and cause Stop/
continue
Action Detailed
information
Diagnostic
timing