36 ERROR CODES
36.4 List of Error Codes
599
36
3C00H Hardware failure A hardware failure has been detected. Stop CPU module
Take measures to reduce noise.
Check the mounting status of the
CPU module, SIL2 function
module, and safety function
module.
Reset the CPU module and run it
again. If the same error code is
displayed again, the possible
cause is a hardware failure of the
CPU module. Please consult your
local Mitsubishi representative.
Redundant function module
The possible cause is malfunction
due to noise. Take measures to
reduce noise by checking the
distance of wires and cables, and
the grounding status of each
device.
Execute a module communication
test. If the same error code is
displayed again, the possible
cause is a hardware failure of the
redundant function module.
Please consult your local
Mitsubishi representative.
Failure
information
Always
3C01H
3C02H At power-on, at
RESET, at
END
instruction
execution, at
interrupt
occurrence
3C03H Always
3C0FH CPU module
Take measures to reduce noise.
Check the mounting status of the
CPU module, SIL2 function
module, and safety function
module.
Reset the CPU module and run it
again. If the same error code is
displayed again, the possible
cause is a hardware failure of the
CPU module or extended SRAM
cassette. Please consult your local
Mitsubishi representative.
Redundant function module
The possible cause is malfunction
due to noise. Take measures to
reduce noise by checking the
distance of wires and cables, and
the grounding status of each
device.
Execute a module communication
test. If the same error code is
displayed again, the possible
cause is a hardware failure of the
redundant function module.
Please consult your local
Mitsubishi representative.
Error
code
Error name Error details and cause Stop/
continue
Action Detailed
information
Diagnostic
timing