616
36 ERROR CODES
36.4 List of Error Codes
4272H Debug related function
error
• The trigger logging specifying the device as a
trigger condition is being performed (data logging
status: RUN waiting (no collection), Condition
waiting (no collection), Start waiting (no
collection), Pause, Collecting, Trigger waiting
(collecting before trigger), Collecting after trigger,
or Saving the logging data).
• Change the trigger condition. Or, stop the trigger logging
being performed (data logging status: RUN waiting (no
collection), Condition waiting (no collection), Start waiting (no
collection), Pause, Collecting, Trigger waiting (collecting
before trigger), Collecting after trigger, or Saving the logging
data), and register another trigger logging.
■When CPU Module Logging Configuration Tool is used
• Change the trigger condition. Or, stop the trigger logging
being performed (data logging status: RUN waiting (no
collection), Condition waiting (no collection), Start waiting (no
collection), Pause, Collecting, Trigger waiting (collecting
before trigger), Collecting after trigger, or Saving the logging
data), and start another trigger logging.
4275H Debug related function
error
• Auto logging is being performed. • After the auto logging, replace the SD memory card and
execute again.
4276H Debug related function
error
• The function that cannot be executed during the
data logging (data logging status: RUN waiting
(no collection), Condition waiting (no collection),
Start waiting (no collection), Pause, Collecting,
Trigger waiting (collecting before trigger),
Collecting after trigger, or Saving the logging
data) was executed.
• Stop the data logging, and then execute the function.
4277H Debug related function
error
• The number of saved files exceeded the
specified number.
■When CPU Module Logging Configuration Tool is
used
• The data logging was started in a state where the
number of saved files has exceeded the specified
number. (The operation when the number of
saved files exceeded is set to "Stop".) Or, the
data logging was started in a state where the
number of saved files has exceeded the specified
number. (The operation when the number of
saved files exceeded is set to "Overwrite".)
• The number of files saved in the storage destination memory
has exceeded the setting value. Delete files, or change the
storage destination and then register.
■When CPU Module Logging Configuration Tool is used
• The number of files saved in the storage destination memory
has exceeded the setting value. Delete files or change the
storage destination, and then start the data logging.
4278H Debug related function
error
• An attempt was made to register data logging in
a state where the saved file number has reached
its maximum, FFFFFFFF. Or, the number
reached to the maximum during the execution.
■When CPU Module Logging Configuration Tool is
used
• The data logging was started in a state where the
saved file number has reached its maximum,
FFFFFFFF. Or, the number reached to the
maximum during the execution.
• The saved file number in the storage target memory has
reached its maximum, FFFFFFFF. Delete files, or change the
storage destination and then register.
■When CPU Module Logging Configuration Tool is used
• The saved file number in the storage target memory has
reached its maximum, FFFFFFFF. Delete files or change the
storage target memory, and then perform the data logging.
427AH Debug related function
error
• The common setting file is corrupted.
■When CPU Module Logging Configuration Tool is
used
• The data logging was started to the memory
where the corrupted common setting file exists.
• Write the common settings to the target memory again.
■When CPU Module Logging Configuration Tool is used
• Write the common settings to the target memory again.
427BH Debug related function
error
• The data logging with the same file storage
destination is being performed (data logging
status: RUN waiting (no collection), Condition
waiting (no collection), Start waiting (no
collection), Pause, Collecting, Trigger waiting
(collecting before trigger), Collecting after trigger,
or Saving the logging data).
■When CPU Module Logging Configuration Tool is
used
• The data logging with the same file storage
destination is being performed (data logging
status: RUN waiting (no collection), Condition
waiting (no collection), Start waiting (no
collection), Pause, Collecting, Trigger waiting
(collecting before trigger), Collecting after trigger,
or Saving the logging data).
• Stop the data logging destined for the same storage, and
then register. Or, change the storage destination of the file,
and then register.
■
When CPU Module Logging Configuration Tool is used
•
S
top the data logging destined for the same storage, and
then perform another data logging. Or, change the storage
destination of the file, and then register.
4282H Debug related function
error
• The registration was performed with the internal
buffer capacity set to 0.
• Check and correct the internal buffer capacity setting.
Error
code
Error name Error details and cause Action