Appendix 5 List of Special Register Areas
SD60 Number of
module with
blown fuse
Number of module with blown
fuse
The lowest number of module in which a fuse blew is stored.
The fuse blown state check is also done for output modules on
the remote I/O station.
In a redundant system with redundant extension base unit, this
register is set as follows:
If a fuse blown is detected in an output module on an extension
base unit, the I/O number is stored only in the CPU module of
the control system, but not stored in the CPU module of the
standby system.
When the systems are switched, the state before system
switching is held.
When the error is cleared, the CPU module of the system
where the error is cleared clears the value.
S (Error)
SD61 I/O module verify
error module
number
I/O module verify error module
number
The lowest I/O number of the module which has an error detected
by the I/O module verification is stored.
I/O module verification is also done for modules on the remote I/O
station.
In a redundant system with redundant extension base unit, this
register is set as follows:
If an I/O verification error is detected in a module on an
extension base unit, the I/O number is stored only in the CPU
module of the control system, but not stored in the CPU module
of the standby system.
When the systems are switched, the state before system
switching is held.
When the error is cleared, the CPU module of the system
where the error is cleared clears the value.
S (Error)
SD62 Annunciator
number
Annunciator number The annunciator number which is detected first is stored. S (Instruction
execution)
SD63 Number of
annunciators
Number of annunciators The number of detected annunciator is stored. S (Instruction
execution)
SD64 to SD79 Table of detected
annunciator
numbers
Detected annunciator number Numbers of activated annunciators are sequentially registered
into SD64 to SD79, each time an annunciator (F) is turned on by
the SET F instruction.
Number of the annunciator deactivated by the RST F instruction
is removed from register areas SD64 to SD79, and the numbers
of annunciators which were lined up behind the removed one
move forward one by one. When the number of detected
annunciators has already reached 16, the number of a newly
detected annunciator is not stored into SD64 to SD79.
For details on the annunciator, refer to the annunciator (F) (
Page 453 Annunciator (F))
S (Instruction
execution)
SD80 Detailed
information 1
information
category
Detailed information 1
information category code
Detailed information 1 information category code is stored.
b0 to b7: Information category code
b8 to b15: Unused (fixed to 0)
The following codes are stored into the information category
code.
0: N/A
1: Program position information
2: Drive number and file name
4: Parameter information
5: System configuration information
6: Number of times information
7: Time information
24: Failure information
27: System switching information
37: Data type (tracking transfer) information
38: Tracking transfer trigger information
46: CPU module data backup/restoration folder information
58: Extension cable information
S (Error)
No. Name Data stored Details Set by
(setting
timing)
b15 b7b8
b0