EasyManua.ls Logo

Mitsubishi Electric MELSEC iQ-R02CPU - Start Address

Mitsubishi Electric MELSEC iQ-R02CPU
416 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
100
1 FUNCTIONS
1.6 Communications Using the Random Access Buffer
Start Address
The start address of the random access buffer range where data read/write is executed is expressed as a logical address.
( Page 97 Physical address and logical address of random access buffer)
When exchanging data with binary codes
Specify the head address with a binary value.
When exchanging data with ASCII codes
Specify the ASCII code for expressing the start address as a hexadecimal.
Data length setting
Express the number of read/write data words with the random access buffer range.
When exchanging data with binary codes
Specify the number of words as a binary value. (Maximum 1017 words)
When exchanging data with ASCII codes
Specify the ASCII code when expressing the number of words as a hexadecimal. (Maximum 508 words)
LH
2 bytes
LH
−−
4 bytes
LH
2 bytes
LH
−−
4 bytes

Table of Contents