1 FUNCTIONS
1.13 Security Function
179
1
Precautions
The following section lists the precautions for using remote password.
Set connection
Set the remote password for the connection used to exchange data with an external device that can execute the unlock/lock
processing.
When remote password is set for UDP/IP connection
Determine the external device to communicate with and exchange the data. (With UDP/IP, after the remote password is
unlocked data can be exchanged with devices other than the unlocked external device too. Determine the communication
device before starting use.)
Always lock the remote password after data communication is finished. (If the remote password is not locked, the unlocked
state is held until timeout occurs.)
Set "UDP" for "Existence Confirmation" of the target connection in "External Device Configuration" under "Basic Settings".
Set as small a value as possible for the "Destination Alive Check Start Interval Timer" and "Destination Alive Check Interval
Timer" in "Timer Settings for Data Communication" under "Application Settings".
TCP/IP close processing
If the TCP/IP is closed before the TCP/IP is locked, the CPU module will automatically start the lock processing.
Remote password valid range
The remote password is valid only for access from the Ethernet-equipped module for which the parameters are set. When
using multiple CPU modules in a multi-CPU system, set a remote password for each CPU module for requiring a remote
password.
The remote password is checked when accessing with path A or B.
The remote password is not checked when accessing with path C or D.
Connection for nonprocedural fixed buffer communication
The remote password is not checked during communication for nonprocedural fixed buffer communication, so do not set the
remote password check.
Accessing another station's programmable controller
When the external device is accessing another station's programmable controller via the Ethernet-equipped module, it may
not be possible to access the programmable controller if a remote password is set for the CPU module at the relay station or
access station.
Ethernet
A
B
C
D
Enable/
Disable
Remote password
check
No remote password
parameter
Remote password
parameter