2 PARAMETER SETTINGS
2.3 Application Settings
275
2
Module Operation Mode
Set the module operation mode.
Set the same operation mode for both of the P1 connector and P2 connector.
For a redundant system, select the module operation mode of system A.
For details on module communication test mode, refer to the following.
Page 284 Module communication test
When different operation modes are set for the P1 connector and P2 connector, the Ethernet-equipped module operates with
the following operation modes.
Item Description Setting range
Module Operation Mode Online
Normal operation mode
Offline
Communication with other stations and dedicated instruction cannot
be performed in this mode. Select this mode to debug the program
while the network is not yet connected.
Module Communication Test
A mode for operating the module communication test. Select this
mode to check the operation when the module is in abnormal
condition.
Online
Offline
Module Communication Test
(Default: Online)
Module Operation Mode Operation mode of Ethernet-equipped
module
P1 connector P2 connector
Online Offline Offline
Module Communication Test Module Communication Test
Offline Online Offline
Module Communication Test Module Communication Test
Module Communication Test Online Module Communication Test
Offline

Table of Contents