3 TROUBLESHOOTING
3.4 Troubleshooting by Symptom
309
3
Communication fails at OPS connection.
When communication using the redundant system function is not possible at the time of an OPS connection, check the
following items and take action.
Check item Action
In "External Device Configuration" under "Basic Settings", is "OPS Connection
Module" set for the external device?
Correct the settings for "External Device Configuration" under "Basic
Settings".
In "External Device Configuration" under "Basic Settings", is the port number
setting correct?
In "External Device Configuration" under "Basic Settings", is the external
device IP address setting correct?