202
1 FUNCTIONS
1.15 Simple CPU Communication Function (RJ71EN71, RnENCPU (Network Part))
When the communication destination is KEYENCE (KV series)
*1 The device is displayed in units of bits. (One point corresponds to one bit.)
*2 Specify 0 or a multiple of 16 at the start of a B device.
Specify 00 in the last two digits at the start of devices other than B, T, or C devices. (The format of devices other than B device consists
of the last two digits of bit specification and the upper digits of word specification.)
When the communication destination is Panasonic (FP2SH series)
*1 The device is displayed in units of words. (One point corresponds to one word.)
*2 The setting can be made only when the communication pattern is "Read".
Set the MEWTOCOL station number on the external device side. At this time, set 1 to the external device side
(FP2) and 2 to the own station side.
Type Applicable device
Symbol Range
Bit device
*1*2
R 0 to 199915
B 0H to 7FFFH
MR 0 to 399915
LR 0 to 99915
CR 0 to 7915
T 0 to 3999
C 0 to 3999
Word device CM 0 to 5999
DM 0 to 65534
EM 0 to 65534
FM 0 to 32767
ZF 0 to 524287
W 0H to 7FFFH
T 0 to 3999
C 0 to 3999
Type Applicable device
Symbol Range
Bit device
*1
WX
*2
0 to 511
WY 0 to 511
WR 0 to 886
WL 0 to 639
Word device LD 0 to 8447
DT 0 to 10239
FL 0 to 32764

Table of Contents