240
1 FUNCTIONS
1.17 Redundant System Function
6. Set the network configuration as follows. The redundant system control system IP address is specified for the send
destination IP address.
[Navigation window] [Parameter] [Module Information] [RJ71EN71] [Port 1 Module Parameter (Ethernet)]
[Basic Settings] [External Device Configuration]
7. Write the set parameters to the CPU module. Then reset the CPU module or power off and on the system.
[Online] [Write to PLC]
In this setting example, default settings are used for the parameters other than those described. For the
parameter setting, refer to the chapter explaining the parameters in this manual. ( Page 241
PARAMETER SETTINGS)