2 PARAMETER SETTINGS
2.3 Application Settings
257
2
*1 When the device type of the communication destination is an "SLMP-compatible device (QnA-compatible 3E frame)", the value is fixed
to 65535ms.
*2 When the device type of the communication destination is an "SLMP-compatible device (QnA-compatible 3E frame)", the value is fixed
to 0.
Communication destination setting
The following table lists the communication destination setting specified for the simple CPU communication.
Bit device Points Set the type, start number, and end number of the "Source" bit
device and the type and start number of the "Destination" bit
device. When these values are input, the number of points will
be displayed automatically.
The setting range differs depending on
the communication destination.
(Page 198 Devices that can be
specified)
Type
Start
End
Word device Points Set the type, start number, and end number of the "Source"
word device and the type and start number of the "Destination"
word device. When these values are input, the number of points
will be displayed automatically.
Type
Start
End
Communication time-out period (ms) Sets the time period until the retry is performed, the time period
until a communication error occurs, and the time period to wait a
response from the communication destination after an error
response from the communication destination.
Configure the setting so that (communication time-out period)
(execution interval).
For details on the communication time-out period, refer to the
following.
Page 206 Communication Time-out Period/Communication
Retry Count/Monitoring Time At Error
10 to 65535ms (in increments of
1ms)
*1
(Default: 1000ms)
Communication retry count Sets the number of communication retry to be performed within
the communication time-out period when the communication
destination returns an error response or does not respond.
For details on the communication retry count, refer to the
following.
Page 206 Communication Time-out Period/Communication
Retry Count/Monitoring Time At Error
0 to 255 times
*2
(Default: 3)
Monitoring time at error (s) Sets the communication time after a communication error
occurred.
For details on the monitoring time at error, refer to the following.
Page 206 Communication Time-out Period/Communication
Retry Count/Monitoring Time At Error
1 to 300s
(Default: 30s)
Comment Sets a comment for the setting number, if required. 32 one-byte characters (16 double-
byte characters) maximum
(Default: Blank)
Item Description Setting range
Device Type Specify the device type of the communication destination. MELSEC iQ-R (built-in Ethernet)
MELSEC-Q (built-in Ethernet)
MELSEC-L (built-in Ethernet)
MELSEC iQ-F (built-in Ethernet)
MELSEC iQ-R (Ethernet module)
MELSEC-Q (Ethernet module)
MELSEC-L (Ethernet module)
SLMP-compatible device (QnA-compatible 3E
frame)
OMRON (CS/CJ series)
KEYENCE (KV series)
Panasonic (FP2SH series)
Panasonic (FP7 series)
YASKAWA MP3000 series
YASKAWA MP2000 series
Yokogawa FA-M3 series
MODBUS/TCP-compatible device
(Default: Blank)
UDP/TCP Set the protocol used for the communication. UDP
•TCP
(Default: Blank)
IP Address Enter the IP address of the communication destination. 0.0.0.1 to 223.255.255.254
(Default: Blank)
Item Description Setting range