1 FUNCTIONS
1.3 Communications Using the Predefined Protocol
43
1
If there are no elements other than length, an element error occurs. (When using length, one or more
elements other than length are required.)
If the calculation result exceeds the number of digits set with "Data Length", the excessive digit value is
discarded (invalidated). For example, if the data length is 2 bytes and the data size calculation results are
"123" bytes, the data length will be "23".
If there is a non-conversion variable (variable length)/non-verified reception (character length variable) after
the length, and that section is not included in the length calculating range, arrange the static data
immediately after the non-conversion variable/non-verified reception.
When the code type setting is "ASCII Hexadecimal", a mismatch will occur if a character string other than
"0" to "9", "A" to "F", and "a" to "f" is received.
Use "0" to "9" or "A" to "F" when converting to ASCII characters during send.
When arranging multiple length elements, none of the length calculating range may overlap.
When arranging multiple length elements, the previous length calculating range may not exceed the
arranged length.
A length element cannot be arranged at the final position of the packet elements.