EasyManuals Logo

Mitsubishi FX1S Series Hardware Manual

Mitsubishi FX1S Series
84 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #68 background imageLoading...
Page #68 background image
FX1S Series Programmable Controllers Diagnostics 7
7-2
7.2 ERROR LED ON (CPU ERROR)
Table 7.2: Error LED Checks
Fault
ERROR
LED ON
Remedy
Reset PLC.
Tu r n p o w e r
OFF, then
ON and
trigger RUN
input.
Possible
results
LED OFF
Has the memory cassette been
installed or removed while the unit
was still powered On?
LED is lit
Remedy
Possible
results
LED is lit
Power OFF
Disconnect
earth/ground
terminal
LED is
flashing
Check for programming error. Ensure the earth/
ground cable is correctly rewired.
Power ON
Remedy
Possible program/scan time error.
Check D8012 for program scan time,
(units 0.2 ms must be less than 0.2
sec, i.e. - data value <2000).
Possible results
D8012 > D8000
POWER
RUN
ERROR
A
A
B
PLC M/C PLC M/C PLC M/C
&& '
B

Other manuals for Mitsubishi FX1S Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi FX1S Series and is the answer not in the manual?

Mitsubishi FX1S Series Specifications

General IconGeneral
ModelFX1S Series
I/O Points10 to 30 points
Program Memory2000 steps
Power SupplyAC
CommunicationRS-422
ExpansionNo expansion
Programming LanguageLadder Logic
Input Voltage100-240V AC
Built-in High-Speed CounterUp to 60 kHz (single-phase)
WeightApprox. 0.3 kg
Dimensions90 x 60 x 75 mm