3   SPECIFICATIONS 
 
3.2 Performance Specifications 
The following table provides the performance specifications of the AJ65SBT-CLB. 
 
Table 
3.2  Performance specifications 
Item Specifications 
Station type  Remote device station 
CC-Link Version  Ver.1.10 
2 stations 
64 points each for RX and RY (16 points are used in the system) 
8 points each for RWr and RWw 
4 stations 
128 points each for RX and RY (16 points are used in the system) 
16 points each for RWr and RWw 
Number of 
occupied 
stations 
8 stations 
(4 occupied stations 
 2 
modules) 
256 points each for RX and RY (32 points are used in the system) 
32 points each for RWr and RWw 
AJ65SBT-CLB connection position  No restrictions 
CC-Link side 
External connection system 
One-touch connector for communication [transmission circuit] (5-pin, 
insulation displacement type connector plug is sold separately) 
<Sold separately> Online connector for communication: A6CON-LJ5P 
  4-point mode  8-point mode  16-point mode 
Maximum number of link points 
Number in parentheses assumes 
use of the same I/O addresses 
224 points (448 points) 
Control 
specifications 
Number of link points per station 
Number in parentheses assumes 
use of the same I/O addresses 
4 points 
(8 points) 
8 points 
(16 points) 
16 points 
(32 points) 
Transmission speed  2.5Mbps/625kbps/156kbps 
Communication system  BITR system (Broadcastpolling   Interval Timed Response) 
Transmission path format  T-branch system 
Error control system  CRC 
Number of connected modules  56 modules 
Remote station number  1 to 56 
AJ65SBT-CLB connection position  Connected at the end of the trunk line 
RAS functions 
Network diagnostics, internal loopback diagnostics, slave station 
separation, automatic return to system 
CC-Link/LT side 
Communication specifications 
Connection cable 1 
Dedicated flat cable (0.75mm
2
X4) 4, VCTF cable 3, high 
flexible cable
4 
Module mounting screw 
M4 
 0.7mm   16mm or more screw 
Tightening torque range 78 to 108N
cm 
DIN rail can also be used for mounting. 
Module mounting direction 
Can be mounted in any of six orientations. 
(No restrictions on mounting directions) 
Voltage  24V DC externally supplied (20.4V DC to 26.4V DC, ripples within 5%) 
Current consumption  0.075A (When 24V DC) 
24V DC power 
supply
2 
Start-time current  0.165A (When 24V DC) 
Level of protection  IP2X 
Common 
Weight 0.09kg 
1 Performance of the CC-Link/LT cannot be guaranteed for use of cables other than the dedicated flat cables, VCTF 
cables and high flexible cables. 
2 Supplied by the dedicated power supply or power supply adaptor of CC-Link/LT. 
3 For VCTF cable specifications, see Table 3.3. 