3 - 6                         3 - 6 
MELSEC-
3   SPECIFICATIONS 
 
3.5 Remote I/O Signals for CC-Link Master Module 
This section explains the I/O signals of the AJ65SBT-CLB for the CC-Link master 
module. 
 
3.5.1 Remote I/O signal list when 2 stations are occupied 
Out of 64 points, 16 points are used as a system area. 
 
Signal Direction: AJ65SBT-CLB   master module  Signal Direction: Master module   AJ65SBT-CLB 
Remote input (RX)  Name  Remote output (RY)  Name 
RXn0 
to 
RX(n 2)F 
Used by CC-Link/LT remote 
RYn0 
to 
RY(n 2)F 
Used by CC-Link/LT remote 
RX(n+3)0 
to 
RX(n
3)9 
Use prohibited 
RX(n 3)A  Error status flag 
RX(n 3)B Remote READY 
RX(n 3)C 
RX(n 3)D 
RX(n 3)E 
RX(n 3)F 
Use prohibited 
RY(n
3)0 
to 
RY(n
3)F 
Use prohibited 
 
POINT 
 
The prohibited devices are used by the system and therefore cannot be used by 
the user. 
If data is written to the buffer memory area corresponding to the prohibited device 
or to the device specified for auto refresh, the functions of the AJ65SBT-CLB 
cannot be guaranteed.