6.6.7 Troubleshooting when input cannot be imported from the CC-Link/LT remote I/O station 
For troubleshooting of the remote device station, refer to the user’s manual for your 
remote device station. 
 
Input cannot be imported 
from the CC-Link/LT remote
I/O station
Is the input 
recognized by the 
AJ65SBT-CLB? 
(Refer to Section 3.7.8)
YES
NO
Complete
1 : Check for a short, reversed connection, wire breakage, insulation displacement status, terminating resistors, overall distance, 
 drop line distance (overall drop line length, maximum drop line length) and peripheral environment (noise, etc.).
Is the input LED on?
YES
Consult your local Mitsubishi 
service center or representative, 
explaining a detailed description 
of the problem.
Are there any 
problems on the line?   1
NO
Is the external wiring normal?
NO
NO (Without problem)
Correct the external wiring.
YES
YES (With problem)
Correct the wiring of the 
communication cables.
Consult your local Mitsubishi 
service center or representative, 
explaining a detailed description 
of the problem. 
Is the 
wiring check correct? 
(Refer to Section 4.8)
YES
NO
Review the program, 
parameters and/or wiring.
Are the station 
numbers overlapping?
YES (Overlapping)
NO (Not overlapping)
Consult the local servicing 
company, dealer or our 
branch office.
Correct the overlapping 
station numbers.   2
2 : When the station number setting of the remote I/O station has been changed, power the whole system off, then on.