3   SPECIFICATIONS 
 
3.6 Concept of the Number of Control Points (Point Mode Setting for CC-Link/LT and 
Number of Occupied Stations Setting for CC-Link) 
This section explains the concept of the settings required for system configuration, i.e., 
point mode setting and number of occupied stations setting. 
The point mode setting sets the number of points that can be controlled for each 
occupied remote station in the CC-Link/LT. 
The point mode has three different modes: 4-point mode, 8-point mode, and 16-point 
mode. If the number of occupied stations is the same, the number of remote stations that 
can be controlled in the CC-Link/LT changes depending on the setting of the point mode. 
Note that, when connecting a remote device station to the CC-Link/LT system, set the 
16-point mode in the point mode setting for the CC-Link/LT. 
 
3.6.1 Setting number of occupied stations  
This section explains a simple setting method of the point mode setting and number of 
occupied stations  setting. 
As the point mode, use the 4-point mode. According to the number of I/O points of the 
remote station, refer to the following table and set the number of occupied stations. 
 
Number of Remote 
Station I/O Points 
Number of Occupied Stations Setting 
of AJ65SBT-CLB 
Point Mode Setting of 
AJ65SBT-CLB 
48 points or less  2 stations 
49 to 112 points  4 stations 
113 to 224 points 
8 stations  
(4 occupied stations 
 2 modules) 
4-point mode 
 
POINT 
 
Since the default setting is the 8-point mode, change it to the 4-point mode. 
 
3.6.2 Setting point mode 
This section explains the point mode setting and the application method for number of 
occupied stations setting. 
 
(1)  If the number of occupied stations is set the same, the number of controllable remote 
stations changes depending on the point mode setting, as the following table shows. 
 
Number of Occupied 
Stations Setting 
2 Occupied 
Stations 
4 Occupied 
Stations 
8 Occupied Stations 
(4 occupied stations   2 modules) 
4-point mode  12 stations  28 stations  56 stations 
8-point mode  6 stations  14 stations  28 stations 
Point mode 
setting 
16-point mode  3 stations  7 stations  14 stations 
 
(2)  If the remote module is the same, the number of occupied stations changes due 
to the point mode. 
For example, if a 16-point module is used, the occupied station number changes 
from 4 occupied stations to 2 occupied stations to 1 occupied station when the point 
mode changes from the 4-point mode to the 8-point mode to the 16-point mode.