8 TROUBLESHOOTING
MELSEC-Q
8 - 54 8 - 54
*1
: Characters in parentheses ( ) indicate the special register numbers where individual information is being
stored.
Error
Code
(SD0)
*1
Error Contents and Cause Corrective Action
Corresponding
CPU
1402
The intelligent function module/special
function module was accessed in the
program, but there was no response.
This suggests the intelligient function
module/special function module , CPU
module and/or base unit is expecting a
hardware fault (Contact your local
Mitsubishi representative.)
QCPU
Rem
The special function module was
accessed during the execution of a
FROM/TO instruction set, but there
was no response.
(When an error is generated, the
program error location corresponding
to the individual information is stored.)
The CPU module, base unit and/or the
special function module that was
accessed is experiencing a hardware
fault.(Contact your local Mitsubishi
representative.)
QnA
1403
There was no response from the
intelligent function module when the
END instruction is executed.
An error is detected at the intelligent
function module.
The I/O module (intelligent function
module) is nearly removed,
completely removed, or mounted
during running.
The CPU module, base unit and/or the
intelligent function module that was
accessed is experiencing a hardware
fault. (Contact your local Mitsubishi
representative.)
Q00J/Q00/Q01
There was no response from the
intelligent function module/special
function module when the END
instruction is executed.
An error is detected at the intelligent
function module/special function
module.
The I/O module (intelligent function
module/special function module) is
nearly removed, completely
removed, or mounted during
running.
The CPU module, base module and/or
the intelligent function module/special
function module that was accessed is
experiencing a hardware fault.
(Contact your local Mitsubishi
representative.)
Qn(H)
QnPH
QnPRH
Rem

Table of Contents