8 TROUBLESHOOTING
MELSEC-Q
8 - 62 8 - 62
*1
: Characters in parentheses ( ) indicate the special register numbers where individual information is being
stored.
*12
: This applies to the CPU mdoule of function version B or later.
Error
Code
(SD0)
*1
Error Contents and Cause Corrective Action
Corresponding
CPU
2000
In a multiple CPU system, a CPU
module incompatible with the multiple
CPU system is mounted.
Replace the CPU module incompatible
with the multiple CPU system with a
CPU module compatible with the
multiple CPU system.
Qn(H)
*12
QnPH
The I/O module status is different from
the I/O module information at power
ON.
I/O module (or intelligent function
module) is not installed properly or
installed on the base unit.
Read the error common information at
the GX Developer, and check and/or
change the module that corresponds
to the numerical value (module
number) there.
Alternatively, monitor special registers
SD150 to SD157 using GX Developer,
and check and replace the module
where the bit of its data is "1".
Q00J/Q00/Q01
I/O module information power ON is
changed.
I/O module (or intelligent function
module/special function module) not
installed properly or installed on the
base unit.
Read the common information of the
error using the peripheral device,
and check and/or change the
module that corresponds to the
numerical value (module number)
there.
Alternatively, monitor the special
registers SD1400 to SD1431 at a
peripheral device, and change the
fuse at the output module whose bit
has a value of "1".
When a GOT is bus-connected to
the main base unit or extension
base unit, check the connection
status of the extension cable and the
grounding status of the GOT.
QnA
Qn(H)
QnPH
QnPRH
Rem
2001
During operation, a module was
mounted on the slot where the empty
setting of the CPU module was made.
During operation, do not mount a
module on the slot where the empty
setting of the CPU module was made.
Q00J/Q00/
Q01
*12
2010
More than applicable number of
extension base units have been
used.
When a GOT was bus-connected,
the CPU module was reset while the
power of the GOT was OFF.
Use the allowable number of
extension base units or less.
Power on the PLC and GOT again.
Q00J/Q00/
Q01
*12
QnPRH
2011
The QA B or QA1S B was used as
the base unit.
Do not use the QA B or QA1S B as
the base unit.