8 TROUBLESHOOTING
MELSEC-Q
8 - 70 8 - 70
*1 : Characters in parentheses ( ) indicate the special register numbers where individual information is being
stored.
*12: This applies to the CPU module of function version B or later.
Error
Code
(SD0)
*1
Error Contents and Cause Corrective Action
Corresponding
CPU
2106
5 or more MELSECNET/H modules
have been installed in a whole
multiple CPU system.
5 or more Q series Ethernet
interface modules have been
installed in a whole multiple CPU
system.
Reduce the number of
MELSECNET/H modules to 4 or
less in the whole multiple CPU
system.
Reduce the number of Q series
Ethernet modules to 4 or less in the
whole multiple CPU system.
Qn(H)
*12
QnPH
5 or more MELSECNET/H modules
have been installed.
5 or more Q series Ethernet
interface modules have been
installed.
The same network numbers or
station numbers exist, in the
MELSECNET/10 network system.
Reduce the number of
MELSECNET/H modules to 4 or
less.
Reduce the number of Q series
Ethernet modules to 4 or less.
Check the network numbers and
station numbers.
Qn(H)
QnPH
QnPRH
Rem
2 or more MELSECNET/H modules
were installed.
2 or more Q series Ethernet
modules were installed.
3 or more Q series CC-Link modules
were installed.
The same network number or same
station number is duplicated in the
MELSECNET/H network system.
Reduce the MELSECNET/H
modules to one or less.
Reduce the Q series Ethernet
modules to one or less.
Reduce the Q series CC-Link
modules to two or less.
Check the network number and
station number.
Q00J/Q00/Q01
5 or more AJ71QLP21 &
AJ71QBR11 modules are installed.
3 or more AJ71AP21/R21 &
AJ71AT21B modules are installed.
The total number of installed
AJ71QLP21, AJ71QBR11,
AJ71AP21/R21, and AJ71AT21B
modules exceeds 5.
The same network numbers or
identical station numbers exist in the
MELSECNET/10 network system.
2 or more master or load stations
exist simultaneously at the
MELSECNET(II) or MELSECNET/B
data link system.
Reduce the AJ71QLP21 and
AJ71QBR11 modules to 4 or less.
Reduce the AJ71AP21/R21 and
AJ71AT21B modules to 2 or less.
Reduce the AJ71QLP21,
AJ71QBR11, AJ71AP21/R21 and
AJ71AT21B modules to a total of 4
or less.
Check the network Nos. and station
Nos.
Check the station Nos.
QnA