8 TROUBLESHOOTING
MELSEC-Q
8 - 98 8 - 98
*1 : Characters in parentheses ( ) indicate the special register numbers where individual information is being
stored.
*12: This applies to the CPU module of function version B or later.
Error
Code
(SD0)
*1
Error Contents and Cause Corrective Action
Corresponding
CPU
3100
In a multiple CPU system, the
MELSECNET/H under control of
another CPU is specified as the head
I/O number in the network setting
parameter of the MELSECNET/H.
Delete the MELSECNET/H network
parameter of the MELSECNET/H
under control of another CPU.
Change the setting to the head I/O
number of the MELSECNET/H
under control of the host CPU.
Q00/Q01
*12
Qn(H)
*12
QnPH
The network parameters of the
MELSECNET/H operating as a normal
station was changed to the control
station, or the network parameter of
the MELSECNET/H operating as a
control station was changed to a
normal station. (The network
parameter is updated on the module
side by resetting.)
Reset the CPU module.
Qn(H)
*12
QnPH
QnPRH
The number of actually installed
modules is different from that
designated in the number of
modules setting parameter of
MELSECNET/H.
The head I/O number of actually
installed modules is different from
that designated in the network
parameter of MELSECNET/H.
Some data in the parameters cannot
be handled.
The station type of MELSECNET/H
has been changed while the power
is on. (RESET RUN is required to
change the station type.)
Check the network parameters and
actual mounting status, and if they
differ, make them matched.
If any network parameter has been
corrected, write it to the CPU
module.
Check the extension base unit stage
No. setting.
Check the connection status of the
extension base units and extension
cables.
When the GOT is bus-connected to
the main base unit and extension
base units, also check the
connection status.
If the error occurs after the above
checks, the possible cause is a
hardware fault. (Contact your local
Mitsubishi representative, explaining a
detailed description of the problem.)
QCPU
Although the QnACPU is a control
station or master station, the network
parameters have not been written.
Correct and write the network
parameters.
If the error occurs after correction, it
suggests a hardware fault. (Contact
your local Mitsubishi representative.)
QnA