8 TROUBLESHOOTING
MELSEC-Q
8 - 100 8 - 100
*1 : Characters in parentheses ( ) indicate the special register numbers where individual information is being
stored.
*12: This applies to the CPU module of function version B or later.
Error
Code
(SD0)
*1
Error Contents and Cause Corrective Action
Corresponding
CPU
3101
The link refresh range exceeded the
file register capacity.
Change the file register file for the one
that enables entire range refresh.
Qn(H)
*12
QnPH
QnPRH
When the station number of the
MELSECNET/H module is 0, the
inter-PLC network parameter setting
has been made.
When the station number of the
MELSECNET/H module is other
than 0, the remote master parameter
setting has been made.
Correct the type or station number of
the MELSECNET/H module in the
network parameter to meet the used
system.
The network No. specified by a
network parameter is different from
that of the actually mounted
network.
The head I/O No. specified by a
network parameter is different from
that of the actually mounted I/O unit.
The network class specified by a
network parameter is different from
that of the actually mounted
network.
The network refresh parameter of
the MELSECNET/H, MELSECNET/
10 is out of the specified area.
Check the network parameters and
mounting status, and if they differ,
match the network parameters and
mounting status.
If any network parameter has been
corrected, write it to the CPU
module.
Confirm the setting of the number of
extension stages of the extension
base units.
Check the connection status of the
extension base units and extension
cables.
When the GOT is bus-connected to
the main base unit and extension
base units, also check their
connection status.
If the error occurs after the above
checks, the cause is a hardware fault.
(Contact your local Mitsubishi
representative, explaining a detailed
description of the problem.)
A multi-remote I/O network was
configured using a module that does
not support the MELSECNET/H multi-
remote I/O network.
Use a module that supports the
MELSECNET/H multi-remote I/O
network.
QnPH
The system A of the MELSECNET/
H remote master station has been
set to other than Station No. 0.
The system B of the MELSECNET/
H remote master station has been
set to Station No. 0.
Set the system A of the
MELSECNET/H remote master
station to Station No. 0.
Set the system B of the
MELSECNET/H remote master
station to any of Station No. 1 to 64.
QnPRH