8 TROUBLESHOOTING
MELSEC-Q
8 - 112 8 - 112
*1 : Characters in parentheses ( ) indicate the special register numbers where individual information is being
stored.
*12: This applies to the CPU module of function version B or later.
Error
Code
(SD0)
*1
Error Contents and Cause Corrective Action
Corresponding
CPU
4100
The instruction cannot process the
contained data.
Read the common information of the
error using the peripheral device,
check error step corresponding to its
numerical value (program error
location), and correct the problem.
Rem
4101
• The designated device number for
data processed by the instruction
exceeds the usable range.
• Alternatively, the stored data or
constants for the devices designated
by the instruction exceeds the usable
range.
• In the settings of write to the host
CPU shared memory, the write
designation disabled area is
specified as the write destination
address.
4102
In a multiple CPU system, the link
direct device (J \ ) was specified for
the network module under control of
another station.
• Delete from the program the link
direct device which specifies the
network module under control of
another CPU.
• Using the link direct device, specify
the network module under control of
the host CPU.
Q00/Q01
*12
Qn(H)
*12
QnPH
• The network No. or station No.
specified for the network dedicated
instruction is wrong.
• The link direct device (J \ ) setting
is incorrect.
• The module No./network No/number
of character strings specified for the
extension instruction is beyond the
allowed range.
Read the common information of the
error using the peripheral device,
check error step corresponding to its
numerical value (program error
location), and correct the problem.
Rem
4103
The configuration of the PID dedicated
instruction is incorrect.
QnA
Q00J/Q00/
Q01
*12
Qn(H)
QnPRH
4104
The number of settings is beyond the
range.
Read the common information of the
error using peripheral device, and
check and correct the program
corresponding to that value (program
error location).
Q4AR