8 TROUBLESHOOTING
MELSEC-Q
8 - 114 8 - 114
*1 : Characters in parentheses ( ) indicate the special register numbers where individual information is being
stored.
*12: This applies to the CPU module of function version B or later.
*15: This applies to the CPU module with the serial No. of first 5 digits "04102" or later.
*18: This applies to the CPU module with the serial No. of first 5 digits "07032" or later.
Error
Code
(SD0)
*1
Error Contents and Cause Corrective Action
Corresponding
CPU
4105
PLOADP/PUNLOADP/PSWAPP
instructins were executed while setting
program memory check
Delete the program memory check
When using the program memory
check, delete PLOADP/PUNLOADP/
PSWAPP instructions.
Qn(H)
*18
QnPH
*18
QnPRH
*18
4107
33 or more multiple CPU dedicated
instructions were executed from one
CPU module.
Using the multiple CPU dedicated
instruction completion bit, provide
interlocks to prevent one CPU module
from executing 33 or more multiple
CPU dedicated instructions.
Q00/Q01
*12
Qn(H)
*12
QnPH
Numbers of execution to the CC-Link
instruction are beyond 32.
Set the numbers of execution to the
CC-Link instruction to 32 or less.
QnA
4108
The CC-Link parameter is not set
when the CC-Link instruction is
executed.
Execute the CC-Link instruction after
setting the CC-Link parameter.
4109
With high speed interrupt setting
execute PR/PRC,UDCNT1,
UDCONT2, PLSY,
PWM,SPD,PLOADP,PUNLOADP,PAW
PP instruction.
Delete the high-speed interrupt setting.
When using high-speed interrupt,
delete the PR, PRC, UDCNT1,
UDCNT2, PLSY and PWM
instructions.
Qn(H)
*15
4111
An attempt was made to perform write
to the CPU shared memory write
disable area of the host station CPU
module with the instruction.
Read the common information of the
error using GX Developer, and check
and correct the error step
corresponding to that value (program
error location).
Q00/Q01
*12
4112
The CPU module that cannot be
specified with the multiple CPU
dedicated instruction was specified.

Table of Contents