8 TROUBLESHOOTING
MELSEC-Q
8 - 134 8 - 134
*1 : Characters in parentheses ( ) indicate the special register numbers where individual information is being
stored.
Error
Code
(SD0)
*1
Error Contents and Cause Corrective Action
Corresponding
CPU
6050
The function inexecutable in the debug
mode or operation mode (backup/
separate mode) was executed.
Execute the function executable in the
debug mode or operation mode
(backup/separate mode).
QnPRH6060
In a redundant system, the operation
mode (backup/separate) differs
between the control system and
standby system.
Match the operation modes of the
control system and standby system.
6061
6062
Both System A and B are in the same
system status (control system).
Power the CPU module (System B)
which resulted in a stop error, OFF and
then ON.
QnPRH
6100
A CPU module tracking memory error
was detected during initial.
Hardware fault of the CPU module.
(Please contact your local nearest
Mitsubishi or sales representative,
explaining a detailed description of the
problem. Change the CPU modules in
order of the standby system CPU
module and control system CPU
module.)
Q4AR
An error (e.g. retry limit exceeded)
occurred in tracking data
transmission.
(This error may be caused by
tracking cable removal or other
system power-off (including reset).)
The error occurred at a startup since
the redundant system startup
procedure was not followed.
Check the CPU module or tracking
cable. If the error still occurs, this
indicates the CPU module or
tracking cable is faulty. (Contact
your local Mitsubishi representative,
explaining a detailed description of
the problem.)
Confirm the redundant system
startup procedure, and execute a
startup again.
QnPRH