8 - 151 8 - 151
MELSEC-Q
8 TROUBLESHOOTING
*1 : Characters in parentheses ( ) indicate the special register numbers where individual information is being
stored.
Error
Code
(SD0)
*1
Error
Messages
Common
Information
(SD5 to 15)
Individual
Information
(SD16 to 26)
LED Status Operating
Statuses
of CPU
Diagnostic
Timing
RUN ERROR
7011
MULTI EXE.
ERROR
Unit No. ---- Off Flicker Stop
At power ON/
At reset
7020
MULTI CPU
ERROR
Unit No. ---- On On Continue Always
7030
CPU LAY.
ERROR
Unit No. ---- Off Flicker Stop
At power ON/
At reset
7031
7032
7035
CPU LAY.
ERROR
Unit No. ---- Off Flicker Stop
At power ON/
At reset