Programmable relay outputs
K11 to K34
97
Overload signal (OL)
The relay output configured as OL is activated when a freely
selectable motor current is exceeded. The OL output is active as
long as the motor current is higher than this threshold.
X To configure a programmable relay output as OL, define the
current under PNU C041 at which, when exceeded, the OL
signal is activated.
X Then, program one of the relay outputs K23-K24 or K33-K34 as
OL output by entering the value 03 under PNU C021 or C022 or
in PNU C026 for signalling relay contacts K11K12.
Figure 93: Relay output K23-K24 configured as OL (overload signal)
r
Figure 94: Function chart for OL (overload signal)
I
M
: Motor current
OL
5...30 V
0
.
250 V
D
K23 K24
OL
PNU C041
I
M
PNU Name Adjustable in RUN mode Value Function WE
Normal Extended
C040 Overload alarm
signal
– j 00 Always 01
01 Only at constant speed
C041 Overload alarm
threshold
0 to 2 x I
e
1)
The current value entered here determines when the OL
overload signal should be activated.
I
e
1)
1) Frequency inverter rated current